Our clients often ask us as series of question in regards to the room integrity testing to data centres and/or server rooms. To help clarify these questions, and more we have written the following article
- Why do I need a room integrity test? The test is a requirement of the British Standard for gaseous fire extinguishing systems – BS EN:ISO 14520. Most fire insurers will require evidence that the test has been conducted and the result is satisfactory.
 - How quickly can a room integrity test be arranged? – Usually within a few days.
 - How long does the enclosure test take? – Usually between 1 and 2 hours.
 - Will the enclosure integrity test set off alarms? – The enclosure test is completely independent of the detection system.
 - Is the room integrity test disruptive? – It is only necessary to stop access to the room for 10-15 minutes. Personnel can continue to work in the room. The enclosure test can be paused if immediate access becomes required.
 - Does equipment such as servers need to be switched off during the enclosure integrity test? no, severs will not need to be switched off during the integrity test.
 - Does air conditioning need to be switched off during the enclosure integrity test? – Recirculation (chiller) units may continue to run. Air supply/extract ducts passing into the enclosure will need to be either dampered closed or will be temporarily sealed.
 - Will I get a certificate if I pass the room integrity test? – It will be issued within a few days. This should be retained for possible inspection by the authorities/insurers. A summary certificate can be issued at the time of enclosure test if required.
 - What happens if the room fails the enclosure integrity test? – An inspection will be conducted to identify leakage paths for remedial sealing. These will be pointed out at the time of the enclosure test and a plan included in the report. It is recommended that a retest be conducted after remedial action to confirm the adequacy of the retention time.
 - Can remedial sealing be done at the time of the enclosure test? – Yes, provided the leakage can be swiftly remedially, or temporarily, sealed.
 - Does APT undertake remedial sealing? – We can do this if requested or the client can arrange remedial sealing themselves.
 - How often should the room integrity test be done? – The relevant British Standard (BS EN:ISO 14520) specifies that the test should be conducted annually as part of routine maintenance.
 
If you have a protected enclosure that requires an integrity test please contact us at info@airpressuretesting.net or call Darren direct on 07775623464.

