The Different Types of Sound Insulation Testing

The Different Types of Sound Insulation Testing

Sound Testing has been mandatory requirement since July 2003. All new build dwellings and conversions which were built after this date require 10% of each party wall/floor construction type to be tested.

Sound Insulation Tests needs to be carried out between pairs of rooms separated by party walls or floors, i.e. in block of flats you would undertake airborne testing across the walls and floors; and impact tests across the floors.

Sound_Testing_Flats

You usually try to undertake testing between the two main habitable rooms, such as living rooms and bedrooms. The sound test procedure involves setting up a noise source in a room on one side of the party wall or floor and measuring the noise on both sides of the partition with a class 1 analyser.

Airborne Sound Insulation Tests

Airborne sound insulation tests may be required between horizontally and vertically separated pairs of rooms. The sound tests are undertaken by using a sound source, amplifier and loudspeaker to generate a high noise level in one room (the source room). Noise measurements are then taken in both the source and receiver rooms using a prescribed number of source and microphone positions.

Sample_Sound__Testing

The background levels in the receiver room are measured and the reverberation time in the receiver room is also measured. From the results, the airborne sound insulation (DnT,w + Ctr) is calculated and compared to the requirements of Approved Document E.

Impact Sound Insulation Tests

For vertically separated rooms Impact sound Insulation testing may also be required. This sound test is undertaken using a “tapping machine”, (as above) which drops a series of weights onto the floor of the upper room. The noise level in the lower (receiver) room is measured for a prescribed number of source and microphone locations. The background levels in the receiver room are measured and the reverberation time in the receiver room is also measured. From the results, the impact sound insulation (L’nT,w) is calculated and compared to the requirements of Approved Document E.

Impact Sound Testing

We use the latest Norsonic equipment, which is class one rating and UKAS calibrated. We are a UKAS and ISO accredited company, so you can be assured all our testing is carried out to the strictest quality controlled standards.

If you would like more information in regards to sound testing please follow our blog at: http://soundtestinguk.blogspot.co.uk/, or contact me (Darren) on 07775 623464 ot email us at info@aptsoundtesting.co.uk

Impact Sound Insulation Testing

Impact Sound Insulation Testing

Impact sound transmission testing is undertaken to floors only. This test is different, a calibrated Norsonic ‘tapping machine’ which comprises of five ‘hammers’ driven up and down by a cam and electric motor is used to “tap” the floor surface by applying a known force on the floor structure. The machine is placed in several pre-determined positions. The resulting noise is measured in the dwelling below, using a sound level meter.

Impact Sound Testing

Thereafter, background noise measurements are made using a class 1 sound level meter in the receiving room and are used to apply appropriate corrections for external sound such as traffic noise. Similarly the reverberation time (the time taken for sound to decay by 60dB) is measured within the receiving room using the sound source and a sound level meter to determine the corrections that must be applied to account for the characteristics and absorptiveness of the room.

The measured noise levels in the receiving room are corrected for background and reverberation characteristics determine the impact sound insulation performance of the floor. For the impact noise the lower the measured level, the better the performance as less sound is being transmitted into the dwelling below.

The time taken to undertake sound testing varies from project to project as no site is exactly the same. Taking into account the standard site conditions impact testing is usually undertaken as part fo a 6 pack test, consisting of  2 airborne wall, 2 airborne floor and 2 impact sound tests. A standard 6 pack test will usually take between two  and three hours, although this is dependent on our engineers having full free uninterrupted access between all the units/rooms under investigation.

If you require sound insulation testing, and/or acoustic design advice then please contact us now at info@aptsoundtesting.co.uk  or phone me (Darren) directly on 07775623464.