Airborne and Impact Sound Tests

Airborne and Impact Sound Tests

You are required to undertake two types of sound testing to comply with Building Regulations Part E, they are Airborne and Impact sound tests. Airborne sound tests are undertake on wall and floors and impact tests are undertaken on floor only.

To test the sound insulation properties of a floor or wall via airborne sound testing, you need to provide a sound source which consists of an amplifier and loud speaker is set up on one side of the wall or floor partition that is to be tested. We then turn the setting to turn on Pink noise. Pink noise sounds like the static that can be heard on a radio that is off station. Pink noise is used  because it is made up of a wall of sound that has a wide spectrum of frequencies. This provides an indication of sound insulation performance for a wide range of sounds that may be experienced within a dwelling from musical instruments to loud TV noise sources.

sound testing

The pink noise is measured in the room which contains the speaker or sound source using a Class 1 Norsonic sound level meter; thereafter the noise is measured on the other side of the wall or floor partition that is being tested. In layman’s terms the difference between these two levels is the amount of sound that is stopped by the sound insulating qualities if the wall or floor partition/s. The result is then corrected and adjusted depending on the echo or reverberation time within the receiving room, and any background noise such as builders work noise etc.

To test the impact sound insulation performance of a floor, a Norsonic tapping machine which consists of five small hammers that are dropped onto the floor to simulate foot fall, is placed on the floor. The resultant noise in the room below is measured with a Norsonic Class 1 sound level meter and the amount of noise that passes through the floor is the impact sound transmission level and is expressed as a single number. This result is then corrected and adjusted depending on the reverberation time of the rooms as well as any background noise to give the impact sound transmission result (LnT,w).

Impact Sound Testing

Both types of sound tests results are then compared to the performance criteria of Approved Document E, which stipulates that airborne sound needs to achieve 45dB for new build & 43dB for conversion projects. To achieve a pass for impact sound testing you need to achieve 62dB for new build & 64dB conversions.

If you have a project that’s needs acoustic design advice or needs precompletion sound testing then please contact us at: info@aptsoundtesting.co.uk or call us directly on 07775623464.

Successful Sound Testing in London

Successful Sound Testing in London 

From the offset careful consideration should be shown to the acoustic design detailing for both conversion and new build projects if you are to achieve a successful sound testing in London at the first attempt.

For instance many of the dwellings in London consist of flats converted from large Victorian houses. At the time of the original build some 100 years ago, designing for sound insulation was not a consideration and so many of the dwellings suffer from adverse noise transference between the floor and wall partitions. This can be extremely stressful to the occupant’s well-being is a major cause for concern.

ACOUSTIC_DESIGN

There are ways to improve the airborne and impact performance by improving the wall/floor partitions ability to reduce the amount of sound transmission from one side of a construction element to the other and subsequently  from dwelling to dwelling. By adding isolation and  mass to the floors and wall construction compliance with Part E for conversion projects can be achieved.

To help our clients achieve successful sound testing we offer the following ‘3 step package’:

  1. Sample Sound Testing of the existing building. This offers an accurate overview of the acoustic performance of the existing partitions which enables us to offer a targeted acoustic design using the sound insulation performance of the existing construction.
  2. Acoustic Design Review of the proposed developments party walls and floors to ensure acoustic details with be sufficient to pass Building Regulations Part E
  3. Site Survey Visits to check that the onsite construction is being undertaken in-line with manufacturer’s guidelines.

In our experience if the acoustic design is taken into consideration from the offset of the project, then it usually results in compliance with Building Regulations Part E.  In many cases sound test failure is down to poor acoustic design and poor workmanship, that is why we offer the 3 step process to achieve successful sound testing on your London project.

If you have a project that requires acoustic design advice or sound insulation testing, then please contact us at: info@aptsoundtesting.co.uk or phone us directly on 07775623464.

The Two Types of Floor Noise

The Two Types of Floor Noise

Under Building Regulations Part E there are two distinct types of floor noise to consider; they are:

  • Airborne Noise (for example speech and music)
  • Impact Noise (for example footsteps directly on the floor above)

By utilising our extensive knowledge of different materials and construction Even if both types of sound appear to be are excessive through the ceiling/floor, then there are some easy acoustic design upgrades that should reduce the sound levels and improve your sound test results. By utilising our extensive knowledge of different materials and construction we can forward a simple, cost effective solution for wall and/or floor upgrade. Where our clients have followed our advice they have achieved a 100% success rate for sound insulation testing – ensuring compliance with Part E of Building Regulations.

noise_flanking

The sound testing procedure is quite simple and our engineer will be happy to explain this on site. Essentially, for party walls there is one type of sound insulation test which is airborne sound test and for compartment floors there are two types of sound insulation tests which are airborne and impact sound insulation tests. The airborne sound insulation test is carried out by means of a loudspeaker emitting a steady source of noise on one side of the partition (wall or floor) to be measured. The corresponding sound level is measured on the other side of the partition. Impact sound insulation tests are carried out by means of a tapping machine placed on the floor sample to be measured and the noise measured in the room or space below

All our engineers carry out the sound test measurements in full accordance with the measurement procedures of BS EN ISO 140-4:1998[3] for field measurements with a single figure DnTw and LnTw in accordance with BS EN ISO 717. As per the new regulations the Spectrum Adaptation Ctr which is a correction factor calculated from the measured DnT.w and the corresponding third octave band DnT values.  It uses a set of weighting levels in third octave bands derived from a road traffic noise spectrum.  It is applied to airborne test results and is measured in dB.

We can carry out final pre-completion sound testing on all new build or conversion projects throughout London. If you would like advice on your acoustic design or sound testing please contact us now at info@aptsoundtesting.co.uk or call me now on 07775623464.

Sound Testing Terminology (2 of 3)

Sound Testing Terminology (2 of 3)

Often confusion can arise from the large amount of ‘terms’ used in conjunction with acoustic design and sound insulation testing. To help with this we have made a list of the following terms for clarity – this is the second of three blogs:

Façade Testing  – This Standard – ISO 140-5:1998) specifies the testing methods to evaluate the sound insulation in buildings and building elements for facades. Three rounds of a proficiency testing scheme for airborne sound insulation measurements have been performed according to the methods specified in the standard for a whole facade by using an external loudspeaker as the noise source.

sound testing equipment

Flanking element (flanking wall) – This is any building element that contributes to the airborne sound or impact transmission between rooms in a building which is not the direct separating element (i.e. not the separating wall or separating floor).

Flanking strip or edge strip – This is a resilient strip using foamed polyethylene normally 5 mm thick, which is located at the perimeter of a floor to isolate the floor boards from the walls and skirting.

Flanking transmission  – This is airborne or impact transmission between rooms that is transmitted via flanking elements and/or flanking elements in conjunction with the main separating elements. An example of a flanking element is the inner leaf of an external wall that connects to the separating ‘core’ of a wall or floor.

Flexible closer – This is a flexible cavity stop or cavity barrier which seals the air path in cavities linking adjoining dwellings.

Floating floor treatment (FFT) – This is a timber floating floor system which may use battens, cradles or platform base, all of which use a resilient layer to provide isolation from the base floor and adjacent wall elements.

Gypsum based plasterboard  – This is a dry lining board applied to walls, ceilings and within floating floor treatments which has gypsum content. It may also have fibre reinforcement within the board.

Impact sound – This is sound which is propagated from a noise source through a direct medium. An example of this is footfall on a floor.

Impact sound transmission – This is sound which is spread from an impact noise source in direct contact with a building element.

We hope the above information in regards to Sound Testing Terminology has been helpful. If you would like more information in regards to acoustic design and sound testing services, please contact us at info@aptsoundtesting.co.uk or visit our website at: www.aptsoundtesting.co.uk

Sound Test Terminology (1 of 3)

Sound Test Terminology (1 of 3)

Often confusion can arise from the large amount of ‘terms’ used in conjunction with acoustic design and sound insulation testing. To help with this we have made a list of the following terms for clarity – this is the first of three blogs:

Absorption – This is the conversion of sound energy into heat, often by the use of a porous material.

Absorbent Material – This is a material that absorbs sound energy, such as acoustic mineral wool.

Airborne sound – This is sound which is propagated from a noise source through the medium of air. Examples of these are speech and sound from a television

Airborne Sound Transmission – This is direct transmission of airborne sound through walls or floors. When sound energy is created in a room, for instance by conversation, some of the energy is reflected or absorbed by room surfaces but some may set up vibrations in the walls and floor. Depending on both the amount of energy and the type of construction, this can result in sound being transmitted to adjacent parts of the building.

Air Path – This is a void in construction elements, which adversely affects the performance of sound resisting construction. Examples of air paths include incomplete mortar joints, porous building materials, gaps around pipes and shrinkage cracks – this can also effect the air tightness results.

Bonded resilient cover – This is a thin resilient floor covering normally of minimum 3-5mm thickness, which is bonded to the isolated screed surface to reduce impact sound transmission such as footfall noise, however it has a lesser effect when it comes to airborne noise.

Cavity stop – This is a proprietary product or material such as mineral wool (fibre) used to close the gap in a cavity wall.

Composite Resilient Batten – This is composed of a timber batten with a pre-bonded resilient material to provide isolation between the flooring surface layers and floor base.

Cradle/Saddle – This is an intermediate support system (with a resilient layer base, either pre-bonded or already integral) using levelling packer pieces to support a timber batten, isolating it from the floor base.

Acoustic_Ceiling_Upgrade

Decibel (dB) – This is the unit used for different acoustic quantities to indicate the level with respect to a reference level.

Density (kg/m3) – This is the mass per unit volume, expressed in kilograms per cubic metre (kg/m3). Blockwork is commonly referred to by industry in terms of strength (in Newtons). However, it is the density that has the important role in terms of sound insulation.

Direct transmission refers to the path of either airborne or impact sound through elements of construction.

DnT,w – This is the weighted standardized level difference. A single-number quantity (weighted) which characterises the airborne sound insulation between two rooms, in accordance with BS EN ISO 717-1:1997

We hope the above information in regards to Sound Test Terminology has been helpful. If you would like more information in regards to our acoustic design or sound insulation testing services, please contact us at info@aptsoundtesting.co.uk or visit our website at: www.aptsoundtesting.co.uk

GOOD ACOUSTIC DESIGN AND CONSTRUCTION

GOOD ACOUSTIC DESIGN AND CONSTRUCTION

Unfortunately there are many misconceptions when it comes to acoustic design and construction. Unfortunately by simply constructing a good separating wall or floor this may not in itself provide sufficient sound insulation to pass the sound testing for Part E as the junctions of each separating wall and/or floor with other parts of the building are equally as important. There may be other potential issues such as flanking sound transmission that can occur via construction components such as:

  1. the internal partitions
  2. the inner leaf of the external wall
  3. the external wall cavities
  4. the external façade or outer leaf
  5. the roof structure
  6. the foundations.

The overall design and construction system should therefore be considered and not just the separating wall or floor partitions.  Flanking sound transmission may in some cases be the dominant pathway between adjoining dwellings, especially in existing buildings where you are planning to convert offices/large houses into flats where there are large existing penetrations through the floors.

NoiseFlankingWall

Also, it is never safe to assume because the architect has specified high performance walls, windows and floor/ceiling assemblies that the materials and onsite workmanship will result in compliance with the anticipated results. You should usually reduce the acoustic target by 4-5dB due to onsite construction. When the construction assembly is tested in the lab, it is also certified and the installation techniques are described and undertaken in great detail.  Unfortunately it is not always possible to replicate the exact conditions on the site compared to the ideal conditions within in a lab setting, which is a far more controlled and scrutinised environment. This is the reason why a 5 point difference is allowed between the construction design on paper and the actual on site sound insulation performance.

APT Sound Testing can advise on all types of acoustic design, whether it’s accomplished during initial construction or during a refurbishment/renovation project.  We have the technical experience to help identify and rectify your soundproofing or noise control problem.

If you would like more information in regards to sound testing please follow our blog at: http://soundtestinguk.blogspot.co.uk or contact us at: info@aptsoundtesting.co.uk or visit our website at: www.aptsoundtesting.co.uk

Broken Down Rating Methods for Sound Testing

Broken Down Rating Methods for Sound Testing 

The sound insulation rating methods that follow are defined in:

Sound insulation testing is usually undertaken near the end of a project to show that the party wall and floor partitions meet the standards shown in Building Regulations Approved Document E.  The method for testing for airborne and impact sound insulation is in full accordance with: the suggested methods presented in BS EN ISO 140-parts 4 & 7: 1998. Sound tests are broken down into various rating methods.

sound testing equipment

The sound insulation rating methods that follow are defined in:

 Rating Method – RW

This single figure rating method is the rating used for laboratory airborne sound insulation tests. The figure indicates the amount of sound energy being stopped by a separating building element when tested in isolation in the absence of any flanking paths.

 Rating Method – DnTw

The single figure rating method that gives the airborne sound insulation performance between two adjacent rooms within a building as measured within site conditions. The result achieved is affected not only by the separating element also by the surrounding structure and junction details.

 Rating Method – Ctr

The Ctr adaptation term is a correction that can be added to either the RW (laboratory) or DnTw (site) airborne rating. The Ctr term is used because it targets the low frequency performance of a building element and in particular the performance achieved in the 100 – 315 Hz frequency range. This term was originally developed to describe how a building element would perform if subject to excessive low frequency sound sources, such as traffic and railway noise. This rating is expressed as RW + Ctr and allows the acoustic designer to critically compare performances. The rating method has not been universally welcomed. Some

acousticians believe that the method is too crude as it only considers the low frequency performance, and because site measurements at low frequencies are prone to difficulties, which can lead to a lack of confidence in the results achieved.

 Rating Method – Lnw

This single figure rating method is the rating used forclaboratory impact sound insulation tests on separating floors. The figure indicates the amount of sound energy being transmitted through the floor tested in isolation, in the absence of any flanking paths. With impact sound insulation, the lower the figure the better the performance.

Rating Method – LnTw

The single figure rating method that is used for impact sound insulation tests for floors. The figure indicates the sound insulation performance between two adjacent rooms within a building as measured on site. The result achieved is affected not only by the separating floor but also by the surrounding structure, e.g. flanking walls and associated junction details.

Rating Method – Dncw

The single figure laboratory rating method, which is used for evaluating the airborne sound insulation performance of suspended ceilings. Laboratory tests simulate the room-to-room performance of the suspended ceiling when a partition is built up to the underside of the ceiling with sound transmitted via the plenum.

APT Sound Testing can advise on all types of acoustic design, whether it’s accomplished during initial construction or during a refurbishment/renovation project.  We have the technical experience to help identify and rectify your soundproofing or noise control problem.

If you would like more information in regards to sound testing please follow our blog at: http://soundtestinguk.blogspot.co.uk or contact us at: info@aptsoundtesting.co.uk or visit our website at: www.aptsoundtesting.co.uk

Noise Flanking Through Steel Columns

Noise Flanking Through Steel Columns.

Unless Steel Columns or beams are isolated from the surrounding wall/floor partition it can lead to noise flanking, particular hollow steel columns. Steel can also provide a strong path for structural impact transmission due to its dense nature.

Pre-conversion sample sound tests should be able to identify whether any columns act as a significant transmission path and whether any acoustic treatment is required to remedy the situation. It may not be necessary to treat the column in all dwellings if flanking is limited, however in many instances the columns will need to be acoustically boxed to prevent sound test failure.

ACOUSTIC_DESIGN

One such acoustic treatment for steel columns or beams would be to construct a free standing metal or timber stud partition around the column, incorporating 50mm insulation quilt and sheeted with two layers of gypsum-based board. Where columns pass through separating floors, as in old bonded warehouses, the junction between column and floor should be well sealed not only for sound insulation but also for fire. The column linings should be double lined with gypsum-based board (minimum mass per unit area 10kg/m2).

Timber beams do not significantly affect the sound insulation performance of a separating floor. However, if a beam has been installed for strengthening, the boxing around the beam may be a single sheet of lightweight board and the board may be fixed directly to the beam resulting in a noise flanking path for airborne and impact sound. This can be resolved by stripping off the boxing, packing any voids with dense mineral wool batt and re-sheeting with two layers of dense gypsum-based sound board.

We hope the above information helps you to understand the potential problems with acoustic design and pre-completion sound testing on your development. If you have a project that’s requires acoustic design advice or sound testing in London, then please contact us at: info@aptsoundtesting.co.uk  or phone us directly on 07775623464.

The two types of sound insulation testing through floors.

There are two distinct types of sound insulation testing through floors, they are:

  1. Airborne Noise (for example speech and music)
  2. Impact Noise (for example footsteps directly on the floor above)

In the event of  both types of sound – Airborne & Impact) are emitting excessive noise through the ceiling/floor, then there are some easy installations that should reduce the sound levels and improve your sound test results.

sound testing equipment

We also offer an acoustic design service which helps clients to pass the sound testing upon completion of the acoustic upgrade. By advising on a simple cost effective wall and/or floor upgrade, we are able to forward simple to follow acoustic design reviews, utilising our extensive knowledge of different materials and construction methods. Where our acoustic upgrades have been incorporated into the site construction, all the pre-completion sound tests have passed, ensuring compliance with Part E of Building Regulations.

Pre-completion sound testing has been a mandatory requirement since 2003 and all new build properties and conversions which were built after this date require 10% of each party wall/floor construction type to be tested. In is usual to test between living rooms and bedrooms as these are classed as the two main habitable rooms; however, other rooms can be used if this is not possible such as study’s, kitchens and dining rooms.

We also carry out a large amount of sound tests in council/housing association blocks, where the residents are experiencing excess noise between the dividing wall and floor partitions.

We provide full UKAS accredited air and sound testing in London, using the latest Class 1 equipment, so our clients can be sure that all testing is completed to a strict ISO quality controlled standard

If you would like advice on your acoustic design or sound testing in London, please contact us now at info@aptsoundtesting.co.uk or call us on 07775623464.

Failed Sound Testing in London?

Failed Sound Testing in London?

When a building fails the Part E Sound Test in London it may be down to a problem with the acoustic construction, this may be down to issues such as noise flanking etc.

Ongoing problems with airborne and structure borne sound are often associated with direct noise flanking transmission through floors and supporting walls and other associated structures such as the external envelope. One common cause of noise flanking and failed sound testing is often associated with the inclusion of lightweight blocks within the construction of the building envelope and/or blocked cavities. It all cases it is essential to establish if your problem is due to direct transmission, flanking transmission or a combination of both so that the most cost effective remedial treatment can be chosen.

Sound Testing in London

Unwanted noise travelling along flanking paths will make the building structure vibrate which causes the sound to radiate into your room. One simple cost effective solution is to build another wall or ceiling in front of the original, but not connected to it (often called an independent wall or ceiling) so it provides isolation between materials.

One way to reduce the chance of flanking transmission is through careful consideration to the design at the start of the project.  Unfortunately, by simply specifying high performance wall and floor partitions it is no guarantee to adequate sound isolation and successful sound insulation testing. APT Sound Testing offer both preconstruction and post construction design solutions to achieve a successful sound testing in-line with Part E of Building Regulations. We also offer onsite inspection services to ensure that the sound insulation elements are being installed as per manufactures guild-lines. Even if both types of sound are emitting through the ceiling/floor then there are some easy installations that should reduce the sound levels and improve your sound test results. By advising on a simple cost effective wall and/or floor upgrade, we are able to forward simple to follow acoustic design reviews, utilising our extensive knowledge of different materials and construction methods

If you have failed a sound test and need acoustic advice on how to overcome the problem then please contact us at info@aptsoundtesting.co.uk or call me direct on 07775623464.