The Two Types of Sound Insulation Test

The Two Types of Sound Insulation Test

There are two types of sound insulation testing, Airborne and Impact.

Airborne sound testing is undertaken to walls & floors. Firstly a controlled noise is generated by an amplifier and loudspeaker across a broad range of frequencies. The generated noise is very loud and is often in excess of 100dB. Initial measurements are taken using a class 1 sound level meter within the ‘source room’ followed by further measurements in the ‘receiver room’ on the other side of the wall or floor under investigation. The source room speaker position is then changed and the measurements repeated either side of the partition under test.

Sound_Insulation_Testing_Equipment

Thereafter background noise measurements are made using a class 1 sound level meter in the receiving room and are used to apply appropriate corrections for external sound such as traffic noise. Similarly the reverberation time (the time taken for sound to decay by 60dB) is measured within the receiving room using the sound source and a sound level meter to determine the corrections that must be applied to account for the absorptive characteristics of the room.

The difference in the two airborne noise levels (for walls and floors), corrected for background and reverberation characteristics determines the airborne sound insulation performance of the wall, or floor. A greater airborne noise difference between the source room and the receiver room determines a higher airborne sound insulation performance.

The time taken to undertake sound testing varies from project to project as no site is exactly the same. Taking into account standard site conditions a set of tests on houses -two airborne walls will take one to two hours. A six pack of tests on flats – 2 airborne wall tests will usually take between one and two hours, although this is dependent on our engineers having full free uninterrupted access between all the units/rooms under investigation.

If you require sound insulation testing, or acoustic design advice then please contact us now at info@aptsoundtesting.co.uk  or phone me (Darren) directly on 07775623464.

Why Have I Failed my Sound Insulation Test?

Why Have I Failed my Sound Insulation Test?

This is one of the most common questions clients ask when their property has just failed the sound testing. One of the main reasons for acoustic partitions failing the Part E sound test is often down to poor isolation of material/s, which can lead to excessive noise flanking. Noise Flanking is a term used by acoustic engineers to describe where sound passes through an acoustic partition due to the abutment of materials. The noise simply hits the one side of the wall and then travels through the construction via a noise bridge. This can be areas such as the incorrect use of masonry wall ties i.e. solid fishtail ties, used in place of specified acoustic wall ties; if your building suffers from noise flanking it may result in a sound test failure.

Sound_Insulation_Testing_Equipment

Unwanted noise travelling along flanking paths can make the building structure vibrate, which can cause sound to radiate into your room – as shown in the plate below . One simple cost effective solution is to build another wall or ceiling in front of the original, to offer extra isolation. For this upgrade to work you need to make sure that the independent wall or ceiling is not directly connected to the existing failed partition; so it provides isolation between materials.

Coupled_wall_construction

Noise flanking can also be down to the use of down to the use of lightweight blocks in the construction of the building envelope. Due to the lightweight mas of the inner wall it allows sound to transmit from dwelling to another, both vertically and horizontally. If a building has failed its sound testing, it is essential to establish if the problem is due to direct transmission, flanking transmission or a combination of both so that the most cost and time effective remedial treatment can be designed and applied to the failed partitions.

If you require more information about acoustic design and/or sound testing on your project, please contact us now at info@aptsoundtesting.co.uk or call me direct on 07775623464.

Sound Insulation Testing

Sound Insulation Testing

At APT we offer Airborne and Impact Sound Insulation Testing in accordance with Part E of the Building Regulations and, where required sound testing on Schools BB93 & BREEAM. Under Part E of Building Regulations, this is a requirement for new and converted dwellings where there is a separating partition wall or floor. The sound insulation testing of existing buildings is carried out to assess current levels of sound insulation and to allow for the design of remedial measures, where the performance needs to be increased.

The buildings that currently require sound testing are:

  1. Dwelling-houses, flats or rooms for residential purposes created by conversion of existing buildings or new build rooms for residential purposes will need to be tested if work starts after 1 July 2004.
  2. New build dwelling-houses and flats will need to be tested if work starts after 1 July 2004.

Sound insulation testing is carried out to ensure that minimum standards of sound resistance have been met to ensure the well-being of new tenants is not compromised by adverse sound transmission. The testing checks that the dividing partitions have not been compromised by poor workmanship and poor design. We use the latest sound testing equipment as shown below:

sound testing equipment

You are normally required to undertake sound testing to each type of construction, i.e. if you have a mixture of brick, block-work, timber and metal stud-work walls all four types would need to be tested, followed by a 10% sample of that type. it is worth noting that if any test failures occur, then the number of sound tests may need to increase on the development.

If you are unsure whether the Regulations apply to your development or if your site needs sound insulation testing, please call your local office or email us at info@aptsoundtesting.co.uk where our team will be happy to discuss all aspects of acoustics or sound insulation within buildings, and explain the testing procedure.

Simple Acoustic Upgrades

Simple Acoustic Upgrades

There are many simple acoustic upgrades you can undertake to improve the sound insulation values of your dwelling. Plate A below shows one cost effective ceiling upgrade that can be undertaken on conversion projects. Firstly retain the existing floor joists – check them for general wear and tare) then above the joists install 22mm chipboard. Above the floor board install an acoustic resilient membrane and above this install the 22mm engineered floor. Within the joist cavity install 100mm AW IsoWool. To the underside of the joists fix a resilient hanger system and below this install two layers of 12.5mm sound boards ensuring that boards have adequate laps. It is worth noting that although the above system should work, it is essential that you contact us before going ahead with any works as each project is different and may require extra acoustic design input.

Plate A – Acoustic Floor Upgrade

Good Conversion Diagram - 15-01-16Also, to try and help our clients achieve compliance with Approved Document E at the first attempt we offer the following 4 step acoustic design package:

  1. Site Survey Visits – to let us view the existing site construction. This allows us to check for potential problematic construction such as inclusion of lightweight blocks in the existing construction. It also lets us check that the installation teams are installing the acoustic materials as per manufacturer’s guidelines.
  2. Sample Sound Testing – of the existing construction. This offers an accurate overview of the acoustic performance of the existing partitions which enables us to offer a targeted acoustic design using the sound insulation performance of the existing construction.
  3. Acoustic Design Review – a full design review of the proposed developments party walls and floors.
  4. Pre-completion Sound Testing to satisfy Approved Document E.

APT Sound Testing can advise on all types of acoustic design, whether it’s accomplished during initial construction or during a refurbishment/renovation project. We also undertake UKAS accredited sound insulation testing providing a ‘one stop’ solution for all your acoustic requirements.

If you would like more information in regards to sound testing please follow our blog at: http://soundtestinguk.blogspot.co.uk or contact us at: info@aptsoundtesting.co.uk and 07775623464 or visit our website at: www.aptsoundtesting.co.uk

Sound Insulation Testing in London

Sound Insulation Testing in London

Unless plans were fully approved prior to 1 July 2003, sound insulation testing will be required on your London development between rooms or spaces that share a common area of separating wall and/or floor as stipulated in Building Regulations Part E for the passage of sound. Sound insulation Testing is not generally required for internal walls and floors within a dwelling-house, flat or room for residential purposes; however all internal partitions should be designed to achieve 40dB.

The buildings that require sound testing are:

  1. Dwelling-houses, flats or rooms for residential purposes created by conversion of existing buildings or new build rooms for residential purposes will need to be tested if work starts after 1 July 2004.
  2. New build dwelling-houses and flats will need to be tested if work starts after 1 July 2004.

The main aim of Sound testing in London is to ensure that minimum standards of sound resistance have not been compromised by poor workmanship and/or poor design. You are normally required to undertake sound testing to each type of construction, i.e. if you have a mixture of brick, blockwork, timber and metal studwork walls all four types would need to be tested, followed by a 10% sample of that type using the equipment shown in Plate A below.

Plate A – Our Sound Test Equipment.

sound testing equipment

For instance, if you have a project with 25 flats you would be required to do 3 x 6 pack of tests; each 6 pack contains 2 airborne wall, 2 airborne floor and 2 impact sound tests; however if any test failures occur, then the number of sound tests may need to increase on the development. When sound test failures occur, then the design and construction of the failed partitions will need to be revisited to try and evaluate the reasons for the failure; thereafter, agreement can be reached on how to rectify problem.

APT Sound Testing can advise on all types of acoustic design, whether it’s accomplished during initial construction or during a refurbishment/renovation project. We also undertake UKAS accredited sound testing providing a ‘one stop’ solution for all your acoustic requirements.

If you would like more information in regards to sound insulation testing please follow our blog at: http://soundtestinguk.blogspot.co.uk or contact us at: info@aptsoundtesting.co.uk and 07775623464 or visit our website at: www.aptsoundtesting.co.uk

Adding Mass to Improve Sound Insulation

Adding Mass to Improve Sound Insulation

Adding mass to improve sound insulation can be one of the most important elements to improving precompletion sound testing results. In summary it basically means you add extra weight/mass to the construction of the acoustic wall and/or floor partition. Materials such as solid block-work masonry is best for wall construction; however it is very important that the block-work envelope is constructed out of solid concrete block work as the use of lightweight block work often ends in sound test failure.

Sound_Insulation_Test_London

 For floor construction, solid concrete floors – min 150mm) are usually the best construction for outright mass; however soundboard, plywood and OSB can be found fairly cheaply and will also do the job – if installed as per manufacturer’s guidelines. It is very important that adequate site supervision is on hand to check the construction of all acoustic partitions.

It is basic physics, so for sound to conduct through a wall, it has to actually move (vibrate) the wall ever so slightly. As a heavier wall is harder to move than a lighter wall then it should vibrate less and turn let through less noise. Soundboard is one of the lowest cost sources of mass available and also one of the most commonly used. Wherever possible its best to use two layers of 12.5mm board with the correct laps to the boards. Although the wall will still vibrate it will be less due to the extra mass.

It’s worth noting that although the added mass improved things and it will be more difficult for sound to move this heavier wall, in many instances you will still hear low frequencies (bass noise) quite easily.

Our next blog covers the last – but not least) element of acoustic design – Damping. If you would like more information in regards to acoustic design and sound insulation testing, please contact us now at info@aptsoundtesting.co.uk or call Darren direct on 07775623464.

Decoupling of Materials

Decoupling of Materials

There are many things to consider with your acoustic design and construction, one of the first – and most important) is the decoupling of materials or also know as isolation of materials. Sound travels easily along direct construction pathways, i.e. if the construction is made up of a wooden wall frame with a layer of plasterboard fixed to either side, with this type of construction the sound has a solid mass of materials to travel across. If we “decouple the materials” it reduces the pathway for vibration and the sound levels drop accordingly.

When we design for acoustic partition construction we obviously want less sound vibration to travel from one side of the wall to the other. It is therefore hugely beneficial if we can decouple the partition framing in our walls and ceilings. Decoupling is a simple, inexpensive and highly effective way to improve the sound insulation results for Building Regulations Part E.  .

There are many types of decoupled construction that in turn offer varying degrees of separation of the drywall on one side from the drywall on the other side. For instance the image below shows a twin wall construction which is far superior to a single stud wall. if you require good sound test results, this is one of the best types of construction.

decoupled_wall_construction

By decoupling the wall studs limits by providing a cavity or break between the two walls reduces the vibration trying to conduct through the wall. although this will improves the airborne results, other improvements will still be required.  So although our decoupled framing system reduces a good deal of vibration, we need to continue to the other 3 elements, absorption, mass, and to damping to reduce the noise more effectively.

Our next blog will consider absorption and how it can make a  large difference to sound test results. If you would like more information to acoustic design and/or sound insulation testing please contact us at: info@aptsoundtesting.co.uk or call Darren on 07775623464.

The Main Sound Proofing Elements

The main Sound Proofing Elements

Coupled Wall Construction

We often get asked ‘how can we improve our soundproofing on our development. The first thing to understand is the basic of soundproofing design and construction. If you understand the basics, you’ll have a more educated view point in regards to the way sound and vibration behaves within your new dwellings. Basically, we want to stop sound and vibration through the walls and floors of your development and one of the best ways of doing this is avoiding coupled wall construction. In general, we are trying to stop vibrations from getting to “your” side of the wall or ceiling.

The plate below shows a typical wall and noise problems associated with it. With this type of construction noise transference is a big problem. If there is even moderate levels of noise on one side of the wall the chances are you will hear it.

coupled_wall_construction

If you look at the red arrows in the above diagram it clearly shows how sound is conducted from one side of the wall to the other. As the wall elements are firmly fixed against each other, i.e. the plasterboard is rigidly connected to the timber, the vibration conducts straight through the whole wall construction.

If you look at the blue waves this indicates airborne transmission. The plasterboard is vibrating back and forth which produces a sound wave in the wall cavity. This, in turn, vibrates the plasterboard on the opposite side of the wall. the whole construction acts like a  huge diaphragm or like a large speaker with both sides of the wall vibrating in unison, which is not ideal.

Our next blog will explain how we can reduce noise transmission by decoupling the wall construction. if you would like more information on our sound testing or acoustic design services please contact us now at: info@aptsoundtesting.co.uk or call Darren direct on 07775623464.

Reducing Noise in Residential Buildings

Reducing Noise in Residential Buildings

We often get asked how noise can be reduced in residential buildings such as apartments or terrace houses. One of the most common problems is noise transmission through the floor and ceiling assemblies in flats and through the wall partitions in houses. The usual noise problems range from airborne noise transmission from voices TVs and music to footfall impact noise caused by high heels on wooden/tiled floors.

Noise_Problems_Failed_Sound_Testing

In most cases for newer residential units many of the problems could have been prevented in the first place, if more attention had been paid to noise control during the design and construction process.   If the acoustic design has not been taken into account from the off-set of the project, then it becomes far more problematic and costly if noise problems are discovered and the partitions fail the sound insulation testing during the per-completion testing.

If you are contemplating the purchase of a unit, do not be afraid to question the contractor and the real estate agents about the sound insulation results for the unit. Ask if any of the units failed during the precompletion testing. In some cases just because a sample of the units had been tested during prior to handover doesn’t mean unit has been sound tested.

If you are not happy with the sound insulation properties of your unit then you may have a case to demand corrective action at the expense of others. If you have a noise problem that is not resolved and you go to sell your unit, you may be compelled to reveal the deficiency to a prospective buyer which may have an impact on the selling price.

If you need acoustic advice on your project, please don’t hesitate to contact us no at: info@aptsoundtesting.co.uk or call me direct on 07775623464.

Our Sound Testing Procedure

Our Sound Testing Procedure

Our sound testing procedure is quite simple and our acoustic engineer will be happy to explain this on site. Essentially, for party walls there is one type of sound insulation test which is airborne sound test and for compartment floors there are two types of sound insulation tests which are airborne and impact sound insulation tests. The airborne sound insulation test is carried out by means of a loudspeaker emitting a steady source of noise on one side of the partition (wall or floor) to be measured. The corresponding sound level is measured on the other side of the partition.

sound testing equipment

Impact sound insulation tests are carried out by means of a tapping machine placed on the floor sample to be measured and the noise measured in the room or space below. Calculations are done based on these measurement and the above mentioned parameters are calculated and compared to the Building Regulations Part E sound insulation requirements for the given type of the building. It is important that the building to be sound tested is completely finished and sealed with no sound leakage through doors and windows.  Please see our check list for sound insulation testing for more information.

The airborne and impact sound insulation tests carried out in full accordance with the measurement procedures of BS EN ISO 140-4:1998[3] for field measurements with a single figure DnTw and LnTw in accordance with BS EN ISO 717. As per the new regulations the Spectrum Adaptation Ctr which is a correction factor calculated from the measured DnT.w and the corresponding third octave band DnT values.  It uses a set of weighting levels in third octave bands derived from a road traffic noise spectrum.  It is applied to airborne test results and is measured in dB.

If you would like advice on your acoustic design or sound testing in London, please contact us now at info@aptsoundtesting.co.uk or call us on 07775623464