Noise Flanking Paths

Noise Flanking Paths

To reduce the chance of sound testing failure, it is imperative that flanking transmission is considered at the design stage to reduce potential noise flanking paths. Good detailing at the design stage will minimise this effect and optimise the overall levels of acoustic privacy achieved. If designing for residential units, design advice on flanking details must be followed to maximise the possibility of achieving the specified acoustic performance. It is imperative that the design advice is followed, otherwise the site sound insulation values may not meet the performance criteria required and subsequent expensive remedial treatment may be required.

sound_transmission_through_floors

Flanking sound is defined as sound from a source room that is not transmitted via the separating building element e.g. the wall or floor partition. The sound is transmitted indirectly via paths such as external walls, windows, doors and internal corridors. One of the easiest ways of dealing with sound flanking issues is to use isolation strips around the perimeter of the partitions at the edges of floors and walls, this should be finished with acoustic sealant

One of the main reasons for flanking sound test failures is when the inner leaf of the perimeter wall is built with light weight blocks. This acts like a large snare drum and the sound simple travels straight up the wall from one flat to the flat above and/or below. Even if you have used a acoustically robust wall and/or floor partition the sound insulation testing may still fail. If you have used lightweight blocks in your onsite construction and the building fails the sound test you may need to construction independent internal plasterboard lining throughout the inner perimeter wall, this should isolate the lightweight blocks and ensure the flanking path is minimized.

If the onsite construction has gaps, cracks or holes it will conduct airborne sounds and can significantly reduce the sound insulation of a construction. For optimum sound insulation a construction must be airtight. Most small gaps can be sealed at the finishing stage using Gyproc jointing compounds. Small gaps or air paths around perimeter Gypframe framework can be sealed with sealant. At the base of the partition, gaps will occur which can be filled with acoustic mastic.

If you would like more information in regards to sound insulation testing and or acoustic design advice, then please call us now at info@airpressuretesting.net or call me (Darren) direct on 07775623464.

Sound Testing Rating Methods

Sound Testing Rating Methods

Sound tests are broken down into various sound testing rating methods. The sound insulation definition and terms are as follows:

Rating Method – RW

This single figure rating method is the rating used for laboratory airborne sound insulation tests. The figure indicates the amount of sound energy being stopped by a separating building element when tested in isolation in the absence of any flanking paths.

Acoustic_Design_Service

Rating Method – DnTw

The single figure rating method that gives the airborne sound insulation performance between two adjacent rooms within a building as measured within site conditions. The result achieved is affected not only by the separating element also by the surrounding structure and junction details.

Rating Method – Ctr

The Ctr adaptation term is a correction that can be added to either the RW (laboratory) or DnTw (site) airborne rating. The Ctr term is used because it targets the low frequency performance of a building element and in particular the performance achieved in the 100 – 315 Hz frequency range. This term was originally developed to describe how a building element would perform if subject to excessive low frequency sound sources, such as traffic and railway noise. This rating is expressed as RW + Ctr and allows the acoustic designer to critically compare performances. The rating method has not been universally welcomed. Some acoustician believe that the method is too crude as it only considers the low frequency performance, and because site measurements at low frequencies are prone to difficulties, which can lead to a lack of confidence in the results achieved.

Rating Method – Lnw

This single figure rating method is the rating used for laboratory impact sound insulation tests on separating floors. The figure indicates the amount of sound energy being transmitted through the floor tested in isolation, in the absence of any flanking paths. With impact sound insulation, the lower the figure the better the performance.

Rating Method – LnTw

The single figure rating method that is used for impact sound insulation tests for floors. The figure indicates the sound insulation performance between two adjacent rooms within a building as measured on site. The result achieved is affected not only by the separating floor but also by the surrounding structure, e.g. flanking walls and associated junction details.

Rating Method – Dncw

This is a single figure laboratory rating method, which is used for evaluating the airborne sound insulation performance of suspended ceilings. Laboratory tests simulate the room-to-room performance of the suspended ceiling when a partition is built up to the underside of the ceiling with sound transmitted via the plenum.

If you have a project that’s needs acoustic design advice or sound insulation testing, then please contact us at: info@aptsoundtesting.co.uk or phone me (Darren) directly on 07775623464.

Sound Testing Definitions and Terms (1 of 2)

Sound Testing Definitions and Terms (1 of 2) 

Sound testing is usually undertaken near the end of a project to show that the party wall and floor partitions meet the standards shown in Building Regulations Approved Document E.  The method for testing for airborne and impact sound insulation is in full accordance with: the suggested methods presented in BS EN ISO 140-parts 4 & 7: 1998. Sound tests are broken down into various rating methods. The sound insulation definition and terms are as follows:

What is Sound Insulation?

Sound is transmitted through most walls and floors by setting the entire structure into vibration. The higher the transmission loss of a wall, the better it functions as a barrier to the passage of unwanted noise. There are two types of sound insulation testing in buildings: airborne and impact.

Airborne Sound

This is sound caused by vibrations which transmit through a medium and reach the ear or some other form of detecting device. Sound is measured in loudness (decibels (dB)) and frequency (Hertz (Hz)). Airborne sound (or airborne noise) is sound that is transmitted through the air.

Noise_Problems_Failed_Sound_Testing

Impact sound

This is sound arising from the impact of an object on a building element – wall, floor, or ceiling. Typical sources are footsteps, jumping, and dropped objects. Impact sound transmission occurs because the impact causes both sides of the building element to vibrate, which generates sound waves.

Flanking Noise Transmission

Flanking is the transmission of sound from a source room to a receiving room by paths other than straight through the separating wall and/or floor partition. For example, impact sound may be transmitted from one room to another through a common timber floor. Other common mechanisms for flanking transmission include suspended ceilings, pipework, ducting, etc. Flanking sound is always present, except in the ‘ideal’ acoustics laboratory. In practice the sound insulation is often limited by the flanking transmission.

If you have a project that’s needs acoustic design advice or sound insulation testing, then please contact us at: info@aptsoundtesting.co.uk or phone me (Darren) directly on 07775623464.

 

Sound Test Procedure

Sound Test Procedure 

The Sound Testing procedure is fairly simple and our engineer will be happy to explain this on site. Essentially, for party walls there is one type of sound insulation test which is airborne sound test and for compartment floors there are two types of sound insulation tests which are airborne and impact sound insulation tests. The airborne sound insulation test is carried out by means of a loudspeaker emitting a steady source of noise on one side of the partition (wall or floor) to be measured. The corresponding sound level is measured on the other side of the partition. Impact sound insulation tests are carried out by means of a tapping machine placed on the floor sample to be measured and the noise measured in the room or space below.

Sound_Insulation_Testing_Equipment

All our engineers carry out the sound test measurements in full accordance with the measurement procedures of BS EN ISO 140-4:1998[3] for field measurements with a single figure DnTw and LnTw in accordance with BS EN ISO 717.

Ongoing problems with airborne and structure borne sound are often associated with direct noise flanking transmission through floors and supporting walls and other associated structures. One common cause of noise flanking is often associated with the inclusion of lightweight blocks within the construction of the building envelope and/or blocked cavities. It all cases it is essential to establish if your problem is due to direct transmission, flanking transmission or a combination of both so that the most cost effective remedial treatment can be chosen.

We offer both pre-construction acoustic design advice and  we can also help if your building has failed the Part E sound test. We also offer onsite inspection services to ensure that the sound insulation elements are being installed as per manufactures guild-lines.

If your require sound insulation testing and/or you would like acoustic design advice on your project, please contact us now at info@aptsoundtesting.co.uk.

Sound Insulation Testing in London

Sound Insulation Testing in London

London is a massive city containing over 9 million people density and high rise apartments. With many living in this overcrowded environment it is essential that noise transference between adjoining properties in kept to a minimum for the occupant’s well-being. One way of ascertaining that a building is in compliance with Building Regulations Part E for the prevention of noise transference, is to undertake Sound Insulation Testing in London.

Sound_Testing_Flats

We have undertaken thousands of sound insulation tests throughout London and the South East on all types of projects from simple flat conversions to large developments containing hundreds of flats. We also undertake Sound Insulation Testing where a lease holder dispute has arisen, i.e. where the buildings lease stipulates that wooden floors should not be used instead of carpets and as a result of the change of floor finish the noise levels have increased – especially the impact noise. We can also undertake sample sound testing to highlight the existing noise levels so a targeted acoustic design can be undertaken.

Plate A – Tapping Machine for Impact Sound Testing

Impact Sound Testing

Currently we are also experiencing a rise in the amount of sound testing required to existing blocks of flats, such as existing council stock. This is hardly surprising as the amounts of noise complaints have more than doubled within the last 10 years due to residents experiencing excess noise between the dividing wall and floor partitions.  By utilising our extensive knowledge of different materials and construction we can forward a simple, explanative cost effective solution for wall and/or floor upgrade. Where our clients have followed our advice they have achieved a 100% success sound test pass rate ensuring compliance with Part E of Building Regulations.

APT Sound Insulation Testing offer both preconstruction and post construction design solutions if a project has failed the sound testing. We also offer onsite inspection services to ensure that the sound insulation elements are being installed as per manufactures guild-lines.

If your require pre-completion sound testing and/or you would like acoustic design advice on your project, please contact us now at info@aptsoundtesting.co.uk.

Impact Sound Insulation Testing

Impact Sound Insulation Testing

Impact sound transmission testing is undertaken to floors only. This test is different, a calibrated Norsonic ‘tapping machine’ which comprises of five ‘hammers’ driven up and down by a cam and electric motor is used to “tap” the floor surface by applying a known force on the floor structure. The machine is placed in several pre-determined positions. The resulting noise is measured in the dwelling below, using a sound level meter.

Impact Sound Testing

Thereafter, background noise measurements are made using a class 1 sound level meter in the receiving room and are used to apply appropriate corrections for external sound such as traffic noise. Similarly the reverberation time (the time taken for sound to decay by 60dB) is measured within the receiving room using the sound source and a sound level meter to determine the corrections that must be applied to account for the characteristics and absorptiveness of the room.

The measured noise levels in the receiving room are corrected for background and reverberation characteristics determine the impact sound insulation performance of the floor. For the impact noise the lower the measured level, the better the performance as less sound is being transmitted into the dwelling below.

The time taken to undertake sound testing varies from project to project as no site is exactly the same. Taking into account the standard site conditions impact testing is usually undertaken as part fo a 6 pack test, consisting of  2 airborne wall, 2 airborne floor and 2 impact sound tests. A standard 6 pack test will usually take between two  and three hours, although this is dependent on our engineers having full free uninterrupted access between all the units/rooms under investigation.

If you require sound insulation testing, and/or acoustic design advice then please contact us now at info@aptsoundtesting.co.uk  or phone me (Darren) directly on 07775623464.

The Two Types of Sound Insulation Test

The Two Types of Sound Insulation Test

There are two types of sound insulation testing, Airborne and Impact.

Airborne sound testing is undertaken to walls & floors. Firstly a controlled noise is generated by an amplifier and loudspeaker across a broad range of frequencies. The generated noise is very loud and is often in excess of 100dB. Initial measurements are taken using a class 1 sound level meter within the ‘source room’ followed by further measurements in the ‘receiver room’ on the other side of the wall or floor under investigation. The source room speaker position is then changed and the measurements repeated either side of the partition under test.

Sound_Insulation_Testing_Equipment

Thereafter background noise measurements are made using a class 1 sound level meter in the receiving room and are used to apply appropriate corrections for external sound such as traffic noise. Similarly the reverberation time (the time taken for sound to decay by 60dB) is measured within the receiving room using the sound source and a sound level meter to determine the corrections that must be applied to account for the absorptive characteristics of the room.

The difference in the two airborne noise levels (for walls and floors), corrected for background and reverberation characteristics determines the airborne sound insulation performance of the wall, or floor. A greater airborne noise difference between the source room and the receiver room determines a higher airborne sound insulation performance.

The time taken to undertake sound testing varies from project to project as no site is exactly the same. Taking into account standard site conditions a set of tests on houses -two airborne walls will take one to two hours. A six pack of tests on flats – 2 airborne wall tests will usually take between one and two hours, although this is dependent on our engineers having full free uninterrupted access between all the units/rooms under investigation.

If you require sound insulation testing, or acoustic design advice then please contact us now at info@aptsoundtesting.co.uk  or phone me (Darren) directly on 07775623464.

Why do my Floors Squeak?

Why do my Floors Squeak?

We often receive complaints from clients in regards to their floors creaking. This is often because the Joists are often spaced too far apart, which can result in a reduction in floor stiffness. Over-notching of joists can also lead to a reduction in floor stiffness and also potential squeaking. Although the floors may pass the airborne and impact sound testing, however it won’t stop the squeaking of the floors under the extra load imposed by people walking above.

sound_transmission_through_floors

Other problems may be down to the contractor using 12mm floor boarding instead of 18mm to the top of the joists, again this may allow the boards to move and squeak. It may also be down to the chipboard not sitting level across the joists, this may down to the  joists being installed at slightly the wrong level or a joist hanger may have been hit or come loose during the build. If the joist has been built into the wall the bearing could be unsatisfactory. it may be as simple as a missing joist, or cut edge unsupported or an over span on the joists.

  • Incorrect bridging of resilient layer by over-long screws/nails
  • Fixings connecting ceiling boards to resilient bars should not bridge to joists
  • Extra wide joist spacing that reduces floor stiffness
  • Platform floor resilient layers damaged by inserting pipes and services within the layers
  • Reduction in stiffness due to use of joist hangers
  • Ceiling boards not staggered
  • Over-notching of joists for services reduces floor stiffness
  • Incorrect omission of flanking strips at floor edge perimeters.

In most cases, due to the complexity of acoustical and noise problems along with an overwhelming variety of material designs and combinations due to varying constructions, it is impossible to cover all problems in a short article such as this; however in our experience if the acoustic design is taken into consideration from the offset of the project, then it usually results in compliance with Building Regulations Part E.

If you have a project that requires acoustic design advice and/or sound insulation testing, then please contact us at: info@aptsoundtesting.co.uk or phone me (Darren) on 07775623464.

HOW MANY SOUND TESTS DO I NEED ON MY PROJECT

HOW MANY SOUND TESTS DO I NEED ON MY PROJECT

Our clients often ask ‘how many sound tests do I need on my project’? Part E stipulates that one set of sound tests needs to be undertaken for every ten flats or houses, provided the construction system is the same, if it’s not then you may be required to undertake a set of tests on each type of construction.

A set means 6  sound tests, this should include two locations where the party element (wall or floor) is tested. This is equivalent to two individual tests when assessing the performance of a wall this means 2 airborne wall, 2 airborne floor and 2 impact sound tests as a minimum wherever possible. Wherever possible tests must be undertaken between habitable spaces (e.g. bedrooms and living rooms. Here is a quick summary of the amount of tests required per type of project.

Semi-Detached Houses:

On a pair of semi-detached houses, two airborne sound insulation tests on a pair of separating walls would be required.

Sound_Testing_Semi_Detached_House

Flats (Up to 10 flats)

On flats a 6 Pack would normally be required, this would usually comprise of two airborne sound insulation tests on separating walls; two airborne sound insulation tests of separating floors and two impact sound transmission tests of separating floors.

Sound_Testing_Flats

Rooms for Residential Purposes (up to 10 Rooms)

On student accommodation, hotel rooms & care homes a set of tests would usually comprise of one airborne sound insulation test of a separating wall; one airborne sound insulation test on a separating floor and one impact sound transmission test of a separating floor

Sound_Testing_Hotels

If you are unsure of the amount of sound tests required on your development, please contact us now at: info@aptsoundtesting.co.uk or call me direct on 07775623464.

Here is a link to our website www.aptsoundtesting.co.uk  which shows you our full range of services in compliance with the latest Building Regulations.

Tips to Pass your Sound Insulation Test

Tips to Pass your Sound Insulation Test

Our clients often get asked for tips in regards to passing their sound testing; here are a few tips to help you pass Building regulations Part E:

  • Ensure all penetrations are fully sealed where they terminate through floors and they are adequately boxed with acoustic quilt and two layers of plasterboard.
  • Avoid the use of lightweight blocks in the inner envelope construction as sound will travel both vertically and horizontally from dwelling to dwelling.
  • The use of resilient suspended ceilings will help improve the performance of the floor partition.
  • Ensure all support steels/timbers are carefully boxed out where they travel from flat to flat vertically and horizontally.
  • Use a high quality resilient acoustic membrane on top of the floor to improve the impact performance of a floor.
  • Ensure that you don’t position sockets back to back in acoustic partitions walls.

architect drafting a house blueprint

There are many factors to consider when considering good acoustic design, and they are usually split up into five key factors. If used together or in various combinations they will improve sound insulation properties over a wide range of frequencies. The main factors are:

  1. Mass
  2. Isolation
  3. Absorption
  4. Resilience
  5. Stiffness

Another potential problem can also be down to noise flanking transmission, especially in existing buildings where you are planning to convert offices/large houses into flats. Here are just a few of the potential noise flanking areas:

  1. Structural Steels
  2. Windows built very close to Internal partitions
  3. Inner leaf of the external wall
  4. External wall cavities
  5. External façade or outer leaf
  6. Roof structure

If you click on this link: http://blogyourbusiness.co.uk/designing-for-sound-testing-in-london/ it will take you to the corresponding article which should help explain this in more detail. Here is a link to our website www.aptsoundtesting.co.uk which shows you our full range of services in compliance with the latest Building Regulations. 🙂